Page 41 - Haddonstone
P. 41

41

Cut ends of galvanised steels must be        8.4.9 	 Sulphate Resistance
coated before use.
                                             Where sulphate resistance is required
Where units are made from two-part           (normally in unprotected ground or ground
mixes, reinforcement shall neither be        containing natural sulphates) the suitability
placed within 10 mm of the interface nor     of the units shall be based on the cement
across the interface of the facing and       type and content.
backing mix, unless the cementitious
binder used in both mixes is identical.      8.4.10 	 Thermal Conductivity

Reinforcement may be required either         When requested by the customer, the
for structural or handling purposes only.    manufacturer/supplier shall declare the
Other metal components may be required       thermal resistance of the units. The value
for fixing or restraint purposes. These      shall be established either by testing or
may or may not be considered as part         from recognised tables.
of the reinforcement.
                                             8.4.11 	 Fire Properties
8.4.7 	 Compressive Strength
                                             Units manufactured in accordance with
The average crushing strength of three       this Standard are non-flammable, non-
cubes tested to BS EN 12390-3 shall not      combustible, do not give off toxic gases
be less than 35 MPa @ 28 days old. No        and can provide a barrier to the spread
individual cube is to have a strength of     of smoke and flame. Standard values
less than 28 MPa.                            should be referred to for the fire resistance
                                             of walls made from units complying with
The figure of 35 MPa represents a 40%        this Standard.
increase in compressive strength over that
indicated in the British Standard and is     8.4.12 	 Sound Insulation
as a result of research carried out by The
University of Dundee. Note:1MPa is equal     The sound insulation provided by cast
to 1N/mm2.                                   stone built with units to this Standard is
                                             predominantly influenced by mass per
8.4.8 	 Capillary Absorption Test (CAT)      unit area. The density of the units will
                                             be declared by the manufacturer on
When sampled and tested in accordance        request to enable mass calculations to
with Appendix 2 with an immersion time       be carried out.
of 10 minutes, the mean coefficient of
water absorption due to capillary action     Other factors such as the shape of the
of the three samples shall not exceed        units and the air-tightness of the wall also
1.0 mg/mm2 with no individual value          have an influence. In general, the sound
exceeding 1.3 mg/mm2.                        insulation of a cavity wall is affected by the
                                             width of the cavity, the type and spacing of
It should be noted that the recent research  the wall ties.
project undertaken in conjunction with
The University of Dundee has identified
that the overall durability of a product
is more likely to be indicated by the
compressive strength than the CAT
figure. The CAT figure is more useful in
determining whether a water proofing/
damp proofing additive has been included.
   36   37   38   39   40   41   42   43   44   45   46